Industry / abnt_codi ABNT CODI

The ABNT CODI is an old energy meter standard used in Brazil.

This code interprets the end user serial output existent in the energy meter. That output externalizes its data blinking an LED as a serial protocol at the baudrate of 110 BPS and uses 8 octects:

Octet Bits Description
001 0-7 Number of seconds to the end of current active demand (LSB)
002 0-3 Number of seconds to the end of current active demand (MSB)
4 Bill indicator. It is inverted at each demand replenishment
5 Reactive Interval Indicator. Inverted at end react interval
6 If 1 means the reactive-capacitive is used to calculate UFER
7 If 1 means the reactive-inductive is used to calculate UFER
003 0-3 Current seasonal segment:
0001 – tip
0010 – out of tip
1000 – reserved
4-5 Type of charging indicator (flag):
00 – Blue
01 – Green
10 – Irrigators
11 – Other
6 Not used
7 If equal 1 means reactive rate is enabled
004 0-7 Number of pulses for active energy of cur dem interv (LSB)
005 0-6 Number of pulses for active energy of cur dem interv (MSB)
7 Not used
006 0-7 Number of pulses for reactive energy of cur dem interv (LSB)
007 0-6 Number of pulses for reactive energy of cur dem interv (MSB)
7 Not used
008 0-7 Inverted bits of xor from previous octects